SERIAL CONNECTIVITY

Moxa MGate MB3270I 2 port

2 port Modbus Gateway with 2KV isolation

Product nr: 107018
57093 57093
Features and Benefits
 
  • Convert between Modbus TCP and Modbus RTU/ASCII
  • 1 Ethernet port and 1, 2, or 4 RS-232/422/485 ports
  • Supports 16 simultaneous TCP masters with up to 32 simultaneous requests per master
  • Easy hardware setup and configuration
 
Overview
The MB3180, MB3280, and MB3480 are standard Modbus gateways that convert between Modbus TCP and Modbus RTU/ASCII protocols. Up to 16 simultaneous Modbus TCP masters are supported, with up to 31 RTU/ASCII slaves per serial port. For RTU/ASCII masters, up to 32 TCP slaves are supported.
 
Standard Modbus network integration
MGate MB3000 standard models include the MB3180, MB3280, and MB3480, and are designed for easy integration of Modbus TCP and RTU/ASCII networks. With these models, Modbus serial slave devices can be seamlessly incorporated into an existing Modbus TCP network, and Modbus TCP slaves can be made accessible to serial masters. The MB3180, MB3280, andMB3480 offer features that make network integration easy, customizable, and compatible with almost any Modbus network.
 
High density, cost effective gateway
The MGate MB3000 can effectively integrate networks with a high density of Modbus nodes. The MB3280 can manage up to 62 serial slave nodes, whereas the MB3480 can manage 124. Each RS-233/422/485 serial port can be individually configured for Modbus RTU or Modbus ASCII operation or even different baudrate, allowing both types of networks to be integrated with Modbus TCP within one package.
 
• LAN Interface
Number of Ports 1
Speed 10/100 Mbps, Auto MDI/MDIX
Connector(s) 8-pin RJ45
Magnetic Isolation Protection 1.5 KV built-in
 
• Serial Interface
Serial Standards RS-232/422/485, software selectable
Number of Ports MGate MB3180: 1
MGate MB3280: 2
MGate MB3480: 4
Connectors DB9 male
RS-485 Data Direction Control ADDC® (automatic data direction control)
ESD Protection ESD Protection: 15 KV for all signals
 
• Serial Communication Parameters
Data Bits 7, 8
Stop Bits 1, 2
Parity None, Even, Odd, Space, Mark
Flow Control RTS/CTS, XON/XOFF
Baudrate 50 bps to 921.6 Kbps
 
• Serial Signals
RS-232 TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422 Tx+, Tx-, Rx+, Rx-, GND
RS-485-4w Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w Data+, Data-, GND
 
• Software
Operation Modes RTU Slave, RTU Master, ASCII Slave, ASCII Master
Utilities MGate™ Manager Suite for Windows 98, ME, NT, 2000, XP, 2003, Vista
Multi-Master and Multi-Drop Master mode: 32 TCP slaves
Slave mode: 16 TCP masters (request queue 32-deep for each master)
Bonus Feature Smart Routing
 
• Physical Characteristics
Enclosure MB3180/3280: Aluminum (1 mm)
MB3480: SECC sheet metal (0.8 mm), IP30 protection
Dimensions Without ears
MB3180: 22 x 52 x 80 mm (0.87 x 2.05 x 3.15 in)
MB3280: 22 x 77 x 111 mm (0.87 x 3.03 x 4.37 in)
MB3480: 35.5 x 103 x 158 mm (1.40 x 4.06 x 6.22 in)
With ears
MB3180: 22 x 75.2 x 80 mm (0.87 x 2.96 x 3.15 in)
MB3280: 22 x 100 x 111 mm (0.87 x 3.94 x 4.37 in)
MB3480: 35.5 x 103 x 181 mm (1.40 x 4.06 x 7.14 in)
 
• Environmental Limits
Operating Temperature 0 to 55°C (32 to 131°F)
Operating Humidity 5 to 95% RH
Storage Temperature -20 to 85°C (-4 to 185°F)
 
• Power Requirements
Input Voltage 12 to 48 VDC
Power Connector MGate MB3180: Power jack
MGate MB3280/3480: Power jack and terminal block
Power Line Protection 1 KV burst (EN61000-4-4: EFT/B), 0.5 KV surge (EN61000-4-5)
 
• Regulatory Approvals
Safety UL (UL60950-1), TÜV (EN60950-1)
EMC CE (EN55022 Class A and EN55024), FCC Part 15 Subpart B Class A
EN61000-4-2 (ESD) Level 2
EN61000-4-3 (RS) Level 2
EN61000-4-4 (EFT) Level 2
EN61000-4-5 (Surge) Level 2
EN61000-4-6 (CS) Level 2
EN61000-4-8 Passed
EN61000-4-11 Passed
EN61000-4-12 Passed
 
• Warranty
Warranty Period 5 years
Details See www.moxa.com/warranty